S 325/323 display and data logger
The universal display and compressed air data logger that can measure, display and record all relevant parameters (Flow, consumption, dew point, pressure, temperature, power consumption, compressor status etc.) in a compressed air system.
Product features
- Sensor inputs
- – 2 inputs for CS-iTEC flow / dew point sensors
- – 2 inputs for analog sensors (0…20 mA, 0…10V, Pt100, pulse)
- – Modbus-Master input for Modbus sensors
- Communication Interfaces
- – USB port
- – Ethernet (Modbus/TCP, CSBus, other fieldbus on request)
- – RS-485 (Modbus/RTU, CSBus, other fieldbus on request)
- Other Signals /Features
- – 2 Alarm relay outputs
- – SD-card for data recording
Technical data
Casing | Size: 118x115x98 mm Panel size: 92×92 Protection class: IP65 |
Power supply | 100…240 VAC, 50-60 Hz, 10 VA |
Interface Option | USB RS-485 (Modbus/RTU, CSBus) or Ethernet (Modbus/TCP, CSBus) |
Alarm output | 2 relay, 230 VAC, 3 A |
Ambient conditions | 0 … 50 ºC |
Sensor input 1 | Up to 2 CS-iTEC sensors: S 400, S 420, S 450, S 452, S 201, S 212, S 215 |
Sensor input 2 | Up to 2 analog sensors: CS-iTEC pressure sensors, CS-iTEC temperature sensor, CS-iTEC amps clamp, 0 … 20 mA, 0 … 10V, Pt100, Pt1000, pulse |
Modbus input | Up to 16 sensors are connectable with Modbus/RTU interface |
Accuracy 1) | Dew point: See sensor specs. Flow: See sensor specs. 0-20 mA: 0.01 mA 0-10 V: 0.01 V Pulse: ±1 digit Pt100: 0.2 ºC Pt1000: 0.2 ºC |
Operation temperature | 0 … 50 ºC |
Storage temperature | -20 … 70 ºC |
Data logger(Option) | 100 million values (4G card) |
Protection | IP65 |